Acson AC Error Codes and Troubleshooting
Acson AC Error Codes and Troubleshooting
Wall Mounted AC Inverter Unit
| Error Codes | Operation / Faulty Indication |
|---|---|
| E1 | Room air sensor contact loose / short. Check room sensor connection / change room sensor |
| E2 | Indoor coil sensor contact open. Check indoor coil sensor connection / change indoor coil sensor |
| E3 | Outdoor coil sensor contact open. Check outdoor coil sensor connection / change outdoor coil sensor |
| E4 | Compressor overload protection / Indoor / Outdoor coil sensor short. If running ampere highly increase, change the compressor. If not, replace the coil sensor |
| E5 | Gas leak. Check for leakage & repair / Top up refrigerant |
| E6 | Pump fault. Clear the clogging at drain pipe. If pump is not working, change the pump |
| E7 | Outdoor coil sensor exist (MS model). Remove outdoor coil sensor |
| E8 | Hardware error (tact switch pin short). Check for the tact switch pin condition |
| E9 | No Feedback from indoor fan. Check indoor fan motor / fan motor wiring |
| EE | EEPROM defrost |
Error Codes for G18 and GS02 – Inverter Y Models
Netware 3C / SLM 9 – Inverter Y Models (Except 5WMY-J/JR)
![]() |
| N3C – SLM 9 – Inverter Y Models |
| Error Codes | Problem |
|---|---|
| 00 | Normal |
| U0 | Insufficient gas |
| U2 | DC voltage out of range |
| U4 | Communication error |
| U7 | Signal transmission error (on outdoor unit PCB) |
| UA | Installation error |
| UF | Communication Error (indoor and outdoor) piping and wiring |
| UH | Anti-freeze function in other room |
| A1 | Indoor PCB error |
| A3 | Water pump error |
| A5 | Antifreeze |
| A6 | Indoor fan motor abnormal |
| C4 | Indoor heat exchanger thermistor short/ open |
| C9 | Indoor room thermistor short/ open |
| E1 | Outdoor PCB error |
| E3 | High pressure protection |
| E4 | Low pressure protection |
| E5 | Compressor motor lock |
| E6 | Compressor start-up error |
| E7 | Outdoor DC fan motor lock |
| E8 | Ac input over current |
| E9 | EXV error |
| EA | 4-way valve error |
| F3 | Discharge pipe overheat |
| F6 | Heat exchanger overheat |
| H0 | Compressor sensor system abnormality |
| H3 | High pressure switch error |
| H6 | Position sensor abnormality |
| H8 | AC current sensor error |
| H9 | Outdoor air thermistor short / open |
| J1 | Pressure sensor error |
| J3 | Compressor discharge pipe thermistor short /open / misplaced |
| J5 | Suction pipe thermistor short/ open |
| J6 | Outdoor heat exchanger |
| J7 | Subcooling heat exchanger thermistor short/ open |
| J8 | Liquid pipe thermistor short/ open |
| J9 | Gas pipe thermistor abnormality |
| LC | Communication error (control PCB and inverter PCB) |
| L1 | Outdoor PCB error |
| L3 | Electrical box temperature rise |
| L4 | Heat sink overheat |
| L5 | IPM error / IGBT error |
| L9 | Stall prevention |
| P1 | Open phase or voltage unbalance |
| P4 | Heat sink thermistor short / open |
| PJ | Capacity setting error |
Sequential Controller (SQ LCD) – SB & RT Multi Compressors
| Error Codes | Faulty Indication |
|---|---|
| E01 | Require manual reset (possible causes) |
| E02 | Compressor 1 high temperature (overload) |
| E03 | Compressor 2 high temperature (overload) |
| E04 | Compressor 3 high temperature (overload) |
| E05 | Compressor 4 high temperature (overload) |
| E06 | Compressor 1 high pressure trip / contact open |
| E07 | Compressor 2 high pressure trip / contact open |
| E08 | Compressor 3 high pressure trip / contact open |
| E09 | Compressor 4 high pressure trip / contact open |
| E10 | Compressor 1 trip/low refrigerant/outdoor abnormal |
| E11 | Compressor 2 trip/low refrigerant/outdoor abnormal |
| E12 | Compressor 3 trip/low refrigerant/outdoor abnormal |
| E13 | Compressor 4 trip/low refrigerant/outdoor abnormal |
| E14 | Room sensor short |
| E15 | Room sensor open |
| E16 | Indoor coil sensor 1 short |
| E17 | Indoor coil sensor 2 short |
| E18 | Indoor coil sensor 3 short |
| E19 | Indoor coil sensor 4 short |
| E20 | Indoor coil sensor 1 open |
| E21 | Indoor coil sensor 2 open |
| E22 | Indoor coil sensor 3 open |
| E23 | Indoor coil sensor 4 open |
| E24 | Outdoor coil sensor 1 short |
| E25 | Outdoor coil sensor 2 short |
| E26 | Outdoor coil sensor 3 short |
| E27 | Outdoor coil sensor 4 short |
| E28 | Outdoor coil sensor 1 open |
| E29 | Outdoor coil sensor 2 open |
| E30 | Outdoor coil sensor 3 open |
| E31 | Outdoor coil sensor 4 open |
| E32 | Compressor 1 de-ice |
| E33 | Compressor 2 de-ice |
| E34 | Compressor 3 de-ice |
| E35 | Compressor 4 de-ice |
Error Diagnosis by Wired Controller (MC301)