Panasonic VRF AC Error Codes and Troubleshooting
Panasonic VRF AC Error Codes and Troubleshooting
Indoor unit is detecting error signal from remote controller (and system controller).
Error Codes | Meaning |
---|---|
E01 | Error in receiving serial communication signal. |
E02 | Error in transmitting serial communication signal. |
E03 | Indoor unit is detecting error signal from remote controller. |
E04 | Error in receiving serial communication signal. When turning on the power supply, the number of connected indoor units does not correspond to the number set. |
E06 | Error of the outdoor unit in receiving serial communication signal from the indoor unit. |
E08 | Indoor unit address setting is duplicated. |
E09 | Remote controller address connector. |
E12 | Starting auto address setting is prohibited. This alarm message shows that the auto address connector CN-A.ADD is shorted while other RC line is executing auto address operation. |
E15 | Error in auto address setting. |
E16 | Error in auto address setting. |
E20 | No indoor unit is connected during auto address setting. |
E24 | Main outdoor unit is detecting error signal from sub outdoor unit. |
E25 | Error of outdoor unit address setting. |
E26 | The number of connected main and sub outdoor units do not correspond to the number set at main outdoor unit PCB. |
E29 | Error of sub outdoor unit in receiving serial communication signal from main outdoor unit. |
E30 | Transmission from outdoor unit faulty. |
E18 | Error of main indoor unit in receiving serial communication signal from sub indoor units. |
L02 | This alarm message shows when the indoor unit for multiple-use is not connected to the outdoor unit. |
L03 | Duplication of main indoor unit address setting in group control. |
L04 | Duplication of outdoor R.C. address setting. |
L05 | Priority set remote controller. |
L06 | Non-priority set remote controller. |
L07 | Group control wiring is connected to individual control indoor unit. |
L08 | Indoor unit address is not set. |
L09 | Capacity code of indoor unit is not set. |
L10 | Capacity code of outdoor unit is not set. |
L18 | 4-way valve operation failure. |
P01 | Thermal protector in indoor unit fan motor is activated. |
P09 | Improper wiring connections of ceiling panel. |
P10 | Float switch is activated. |
P12 | Operation of protective function of fan inverter |
P03 | Incorrect discharge temperature. (Comp. No. 1) |
P04 | The internal circuit of the high pressure switch is dead |
P05 | Power supply circuit failure, missing-phase detection. |
P13 | There is a trouble with the outdoor unit when the liquid valve and the gas valve are closed. |
P14 | O2 sensor (detects low oxygen level) activated |
P16 | Compressor running failure resulting from missing phase in the compressor wiring, etc. |
P22 | Outdoor unit fan motor is unusual. |
H31 | IPM trip (IPM current or temperature) |
P29 | Missing-phase/reverse-phase in the compressor wiring, Compressor start-up failure |
F01 | Indoor coil temp. sensor (E1) |
F03 | Indoor coil temp. sensor (E3) |
F10 | Indoor suction air (room) temp. sensor (TA) |
F11 | Indoor discharge air temp. sensor (BL) |
F04 | Compressor No. 1 discharge gas temp. sensor (TD) |
F07 | Outdoor No. 1 coil liquid temp. sensor (C1) |
F08 | Outdoor air temp. sensor (TO) |
F12 | Compressor intake port temperature sensor (TS) |
F16 | High pressure sensor failure |
F29 | EEPROM on indoor unit PCB failure |
F31 | EEPROM on the outdoor unit PCB is a failure. |
H01 | Overcurrent of power supply current (CT) sensor |
H02 | PAM failure |
H03 | Power supply current (CT) sensor failure |
C05 | Indoor or main outdoor unit is not operating correctly. Mis-wiring of control wiring between indoor unil, main outdoor unit and system controller. |
C06 | Indoor or main outdoor unit is not operating correctly. Mis-wiring of control wiring between indoor unit, main outdoor unit and system controller. CN1 is not connected properly. |
P30 | When using wireless remote controller or system controller, in order to check the alarm message in detail, connect wired remote controller to indoor unit temporarily. |