Samsung RAC and FJM Fault Codes

Samsung RAC and FJM Fault Codes

Samsung Air Conditioning Systems ~ FJM (Free Joint Multi) and RAC Operation;

Samsung RAC and FJM Fault Codes 

The table below give indication about self diagnostic routine. Some of error code requires activities exclusively for Authorise Service Center.
Wired remote controller:
Error CodeContents-Measure
101Indoor unit communication error. Check the communication cable of indoor unit. Check the DC output voltage at the communication terminal.
108Duplicated addresssetting error. Check addresssetting of Indoor units
109No response error address from indoor unit. Check indoor unit's quantity setting in outdoor unit. Check electriacl connection and setting.
121Indoor temperature sensor (open/short error). Check indoor unit room temperature sensor. Check indoor unit PCB connector CN41. (White)
122Indoor unit Eva In sensor (Open/Short). Check indoor unit pipe sensor. Check indoor PCB connector CN41.(White)
153Indoor floating switch secondary detection. Check indoor unit floatsensor. Check indoor PCB connector CN5. (black)
202Indoor/outdoor communication error (1 min). Check the communication connection between indoor and outdoor units. Check the power line and communication cable connection status
203Communication error between indoor/outdoor INVlMAIN MICOM (1 min). Check MAIN MICOM . Check INVERTER MICOM.
221Outdoor temperature sensor error. Check sensor connection status. Check sensor location. Check sensor resistance
231COND temperature sensor error. Check sensor connection status. Check sensor location. Check sensor resistance.
251[Inverter] Emission temperature sensor error. Check sensor connection status. Check sensor location. Check sensor resistance.
403Detection of Indoor Freezing (when Comp. Stops). Check whether the indoor unit air intake is blocked. Check the operation of the indoor fan.
404Protection of Outdoor Overload (when Comp. Stops). Check sensor connection status. Check sensor location. Check sensor resistance
416Emission temperature excessively high. No error. (DISCHARGE temperature control)
422High pressure blockage error (Refrigerant completely Leakage error). Check whether the outdoor unitservice valve is open. Check the connection of the pipes. Check the operation of the EEV. Check for refrigerant leakage. (Completely leakage).
440Heating operation blocked. Check the operation setting state. Check temperature sensor.
441Cooling operation blocked. Check the operation setting state . Check temperature senso.
458Outdoor fan 1 error. Check input power connection status. Check the connection status between the motor and outdoor unit PCB. Check indoor/outdoor fuse.
461[Inverter] Compressorstartup error. Check the compressor connection status. Check the resistance between difference phases of the compressor
462[Inverter] Total current error/ PFC over current error. Check the input power Check the coolant charging status Check the normal operation of outdoor fan
463OLP Overheat and Comp. Stop. Reconfirm the opening of the service valve. Check for leaksfrom the connection part of the pipe and product or from the pipe joint. Change the outdoor unit location and direction. Refill the coolant after checking the leaking part. Reinstall the outdoor unitset.
464[Inverter] IPM over current error. Check coolant charging Check the compressor connection status and normal operation Check the obstacles around the indoor and outdoor units Check whether the outdoor unitservice valve is open Check whether the indoor/outdoor installation pipe/ wiring are correct
465Compressor V limit error. Check the compressor connection status Check the resistance between difference phases of the compressor
466DC LINK over/low voltage error. Check input power Check AC power connection
467[Inverter] Compressor rotation error. Check the compressor connection status Check the resistance between difference phases of the compressor
468[Inverter] Currentsensor error. Check EEPROM DATA Check the normal operation of PCB
469[Inverter] DC LINK voltage sensor error. Check the input power connection Check the status of RY21 and R200 in the INVERTER PCB
470EEPROM Read/Write error
471[Inverter] OTP error. Check EEPROM DATA Check the normal operation of PCB
472AC ZERO CROSSING SIGNAL OUT error. Check the input powerstatus
473Compressor LOCK error. Check the compressor connection status Check the resistance between difference phases of the compressor
475Outdoor fan 2 error. Check the input power connection status Check the connection status of the motor and the outdoor unit PCB Check the indoor/outdoor unit fuse
500IPM Overheat Error for Outdoor Unit Inverter Comp. Change the location of the outdoor unit if the temperature is abnormally high when the heatproof plate is checked. Reconnect the screws. Replace the outdoor unit fan. Replace the PBA of the outdoor unit
554Gas leak error. Check the coolant charging status Check the indoor EVA sensor Check if the outdoor unitservice value is open Check that the indoor/outdoor installation pipe/wiring are correct
556Capacities not matched. Check the option code of the indoor unit
601Communication error between the indoor unit and wired remote controller. Check the connection wire between the indoor unit and the wired remote controller
602Communication error between the Master and Slave wired remote controllers. Check the option switch for defining the Master and Slave (only one Master and one Slave can exist)
606COM1/COM2 crossinstallation error. Check that wired remote controller is connected to the COM2 terminal of the indoor unit
EAWired remote controller COM2 option setting error. Check that Com1, Com2 setting DIP switch isset to Com2

Samsung RAC and FJM Fault Codes
Samsung RAC and FJM Fault Codes

Outdoor Unit
Error Code is for reference (S-net), not display on the HUB PCB of Outdoor unit
Error CodeExplanation
E190Pipe inspection error
E199Error of non-performed installation-test-operation
E201The number of indoor unit mismatched
E202Communication errer between the outdoor and indoor unit
E203Outdoor communication error between main micom and inverter micom
E206Outdoor communication error beween main micom and hub micom
E221Outside temperature sensor error (Short/Open)
E237Condenser temperature sensor error (Short/Open)
E251Compressor Discharge temperature sensor error (Short/Open)
E320Compressor OLP sensor error (Short/Open)
E330EvaIn1 Sensor error (Short/Open)
E331EvaIn2 Sensor error (Short/Open)
E332EvaIn3 Sensor error (Short/Open)
E333EvaIn4 Sensor error (Short/Open)
E334EvaIn5 Sensor error (Short/Open)
E335EvaOut1 Sensor error (Short/Open)
E336EvaOut2 Sensor error (Short/Open)
E337EvaOut3 Sensor error (Short/Open)
E338EvaOut4 Sensor error (Short/Open)
E339EvaOut5 Sensor error (Short/Open)
E401Outdoor unit freezing - Safety control (Compressor stop)
E404Outdoor unit overload - Safety control (Compressor stop)
E440High temperature(over 30°C) or low temperature(under -10C) of outdoor as heating mode
E441Low temperature(under -10°C) of outdoor as cooling mode
E416Outdoor unit high discharge temperature - Safety control (Compressor stop)
E458Outdoor Fan Error
E461Inverter compressor starting failure (5 times)
E462Compressor trip by input current control mode (PFC over current)
E463Compressor trip by OLP temperature control mode
E464DC Peak system error (Over current)
E465Compressor Vlimit Error
E466Inverter DC link Voltage error (under 150V, over 410V)
E483H/W Detect DC Link over voltage Error
E467Abnormal compressor running (Compressor Rotation Error)
E468Current sensor error (Short/Open)
E469DC-Link valtage sensor error (Short/Open)
E488Error of the input current sensor
E470Outdoor unit EEPROM Error
E471Inverter micom option read/write error
E474Inverter IPM Heat Sink sensor error (Short/Open)
E485Inverter input current sensor error (Short/Open)
E484PFC Overload error (Over current)
E500Inverter IPM over heat error
E554The refrigerant leaks completely from the outdoor unit